Carbon Monoxide Transmitter: AVC-110 Series AECL

Provides switchable analog signal output (DC 4 to 20mA and 0 to 10V) or RS485 Modbus RTU interface, with an additional dry contact for activating ventilation systems when CO levels exceed 50ppm.

Application

  • Indoor / underground parking.
  • Basement.
  • Garage.
  • Residential apartment.
  • Factory.
  • Boiler room.
  • Indoor places where would be required to detect CO concentration.
AVC-110_Catalog AVC-110-0-10V_Manual AVC-110-CO-4-20mA_Manual AVC-110-RS485-Modbus-RTU_Manual +(84) 839 606 568

The Carbon Monoxide Transmitter uses an electrochemical sensing element to reliably monitor CO concentration in areas such as loading docks, underground parking, basements, garages, or boiler rooms. It offers switchable measurement ranges of 0 to 100ppm and 0 to 250ppm, with an optional high range of 30 to 1000ppm.

Detail Up to top

Specification

ModelAVC-110
Measuring methodChemical-electro
Response timeτ90 ≦ 30 sec.
Accuracy (at 25℃)±5% for 0 ~ 100ppm; ±10% for 100 ~ 500ppm
Resolution1ppm
RepeatabilityReading ± 2 %
DriftZero: <±5ppm; Span: ≦5% / year
Measuring range selection0 ~ 100ppm / 0 ~ 250ppm / 0 ~ 500ppm
Coverage areaAbout 465m2 (2)
Signal outputDC 4~20mA / DC 0~10V, RS-485 (Modbus RTU)                                                    LoRa (Peer to Peer), radio frequency band: 862 ~ 932 MHz(3)
Alarm outputRelay output N.O,N.C (2A / 30V DC ; 0.5A / 125V AC); Relay setting 50 pp
Linearity error<10 ppm (at -20℃ ~ 50℃)
Calibration interval (recommended)12 months
Sensor lifespan4 years(4) typical
Pressure range1 atm ± 10 %
Display (optional)LCD display
Environmental -10℃ ~ 50℃; 15 ~ 90%RH (non-condensation)
Storage-10℃~ 50℃ (14 ~ 122℉)
Warm-up time≤ 1.5 min. (Full scale,≤ 15 minutes)
Power supplyDC 12 ~ 36V, AC 24V (50/60Hz)
Power consumption 4~20mA, 0~10V, RS485: 0.2W (Max.); LoRa / RS485: 1.2W (Max.)
InstallationWall-mount
Case materialFireproof ABS
IP ratingIP30 (No protection from liquids)
CertificationsCE, FCC
  Note:
  • For special measurement range of 0~1000ppm, please contact our sales representative.
  • The coverage area should be considered individually to account for the particular layout and any varying or enclosed spaces. It is recommended to install at least one device in each room.
  • The frequency channels will be differed by country and this frequency can be configured accordingly from 862 to 932Hz.
  • The lifespan of sensor might vary depending on environmental conditions. For example, high ambient temperature will shorten its lifespan.

Feature

  • Measurement: CO
  • Measurement principle: Chemical-electro
  • Installation: Wall-mount
  • Protection: IP30
  • Optional LCD display.
  • CE & FCC Certifications.
  • Maintenance-free for normal indoor applications.

Related products Up to top

HEADQUARTERS

Address: 729 Ba Thang Hai St., Dien Hong Ward, HCM City

Email: info@bkic.vn

Website: https://bkic.vn

HỒ CHÍ MINH OFFICE

Address: No. 4, Street 59, Binh Trung Ward, Ho Chi Minh

Email: info@bkic.vn

Website: https://bkic.vn

HÀ NỘI OFFICE

Address: No. 35, Lane 45, Tran Thai Tong Street, Cau Giay Ward, Ha Noi

Email: info@bkic.vn

Website: https://bkic.vn

Our clients