+(84) 839 606 568The AVC-M Indoor Air Quality Transmitter features high-quality sensors for measuring temperature, humidity, CO, CO2, PM2.5, PM10, TVOC, HCHO, oxygen, and NH3. With an RS485 Modbus RTU signal output, it is ideal for HVAC and BMS systems, offering a compact design for flexible integration. Recommended installation height is 1 to 2 meters above floor level.
| Parameters | Temperature, Humidity, CO2, CO, HCHO, TVOC, PM2.5, PM10, O2, O3, NH3, H2S, NO2, CL2 |
| Signal output | RS485 or RS485 / LoRa (Peer to Peer) switchable, LoRa frequency band: 862 ~ 932 MHz(1) |
| Warm-up time | 15 minutes |
| Operating environment | -10 ~ 50℃ (14~122℉) / 0 ~ 95%RH, non-condensing |
| Storage temperature | -10 ~ 50℃ (14~122℉) |
| Power supply | DC 12 ~ 36V, AC 24V (50/60Hz) |
| Power consumption | RS485: 3W (Max.); LoRa / RS485: 4.5W (Max.) |
| Certifications | CE, FCC |
| IP rating | IP30 (No protection from liquids) |
| Case material | Fireproof ABS |
| Weight | 125g |
| Temperature Measurement | Humidity Measurement | |
| Sensing element | CMOS sensing element | CMOS sensing element |
| Measurement range | -10.00 ~ 50.00℃ (14~122℉) | 0 ~ 99.99%RH |
| Accuracy | ± 0.3℃ (typical) | ± 3%RH (typical) |
| Resolution | 0.01℃ | 0.01%RH |
| Repeatability | ± 0.1℃ | ± 0.1%RH |
| Response time | 5 ~ 30 sec. (τ63%, 25℃) | < 8 sec. (τ63%, 25℃) |
| Long-term drift | < 0.04℃ / year | < 0.5%RH / year |
| CO Measurement | HCHO Measurement | |
| Measurement principle | Electro-chemical | Electro-chemical |
| Measurement range | 0 ~ 100 ppm | 0 ~ 3.00 ppm |
| Accuracy (at 25℃) | ± 5% | ± 5% |
| Resolution | 1 ppm | 0.01 ppm |
| Repeatability | Reading ± 2% | < ± 0.05 ppm |
| Response time | τ90≦30 sec | τ90 < 120 sec. (HCHO: 1 ppm) |
| Drift | Zero: < ± 5 ppm; Span: ≦5% reading / year | Zero: < 0.05 ppm; Span: < 20% reading / year |
| CO2 Measurement | VOC Measurement | |
| Measurement principle | NDIR with automatic calibration | CMOS sensing element |
| Measurement range | 0 ~ 9999 ppm | 0 ~ 500 VOC Index points 0 ~ 500 ppb |
| Accuracy | 0 ~ 2000 ppm (± 30 ppm ± 3% of reading), 2001~9999 ppm (± 70 ppm ± 3% of reading) | < ± 15 VOC Index points; < ± 20 ppb |
| Resolution | 1ppm | 1 VOC Index points; 1 ppb |
| Repeatability | ± 20 ppm+ (± reading *1%) | < ± 5 VOC Index points; < ± 15 ppb |
| Response time | 2 minutes by 90% | < 10 sec. (τ63%) |
| Maintenance | Maintenance-free for normal indoor applications | |
| PM2.5 Measurement | PM10 Measurement | |
| Measurement principle | Laser distributing | Laser distributing |
| Measurement range | 0 ~ 600 μg/m3 | 0 ~ 600 μg/m3 |
| Accuracy | 0 ~ 100 μg/m3 (± 10 μg/m3), 100 ~ 600 μg/m3 (± 10%) | 0 ~ 100 μg/m3 (± 10 μg/m3), 100 ~ 600 μg/m3 (± 10%) |
| Resolution | 1 μg/m3 | 1 μg/m3 |
| Response time | ≦10 sec. | ≦10 sec. |
| Maintenance | Maintenance-free for normal indoor applications | Maintenance-free for normal indoor applications |
| O2 Measurement | NH3 Measurement | |
| Measurement principle | Electro-chemical | Electro-chemical |
| Measurement range | 0 ~ 30% | 0 ~ 50.0 ppm |
| Accuracy | Full scale ± 5% | ± 5% |
| Resolution | 0.01% | 0.1 ppm |
| Repeatability | Reading ± 5% | ± 10% |
| Response time | τ90≦15 sec. | τ90≦90 sec. |
| Drift | <2% / month | Zero: < ± 10 ppm / year; Span: < 2% reading / month |
| CL2 Measurement | H2S Measurement | |
| Measurement principle | Electro-chemical | Electro-chemical |
| Measurement range | 0 ~ 5.00 ppm | 0 ~ 50.0 ppm |
| Accuracy | ± 5% for 0 ~ 5.00ppm | ± 5% for 0 ~ 50.0ppm |
| Resolution | 0.01 ppm | 0.1 ppm |
| Repeatability | Reading ± 2% | Reading ± 2% |
| Response time | τ90≦30 sec | τ90≦60 sec |
| Drift | ≦2% / month | Zero: < ± 0.1 ppm / year; Span: < 10% reading / year |
| O3 Measurement | NO2 Measurement | |
| Measurement principle | Electro-chemical | Electro-chemical |
| Measurement range | 0 ~ 5.00 ppm | 0 ~ 5.00 ppm |
| Accuracy | ± 5% for 0 ~ 5.00ppm | ± 5% for 0 ~ 5.00ppm |
| Resolution | 0.01 ppm | 0.1 ppm |
| Repeatability | Reading ± 2% | Reading ± 2% |
| Response time | τ90≦30 sec | τ90≦30 sec |
| Drift | ≦10% / year | ≦10% / year |
The PM2.5 Transmitter measures particulate matter levels from 0 to 600 μg/m³ with high accuracy, using a state-of-the-art laser scattering sensing element that ensures long-term stability. It is designed for indoor use with a compact, easy-to-install enclosure. PM2.5 Transmitter: AVC-210 Series AECL Explore now
The AVC-810 HCHO Transmitter uses advanced electrochemical sensing technology to measure formaldehyde gas (0-3ppm) with precision. It features an industrial-standard RS485 interface using the Modbus RTU protocol, enabling continuous monitoring and data transfer for indoor air quality analysis. HCHO Transmitter: AVC-810 Series AECL Explore now
The wall-mounted PM10 Air Quality Transmitter uses microprocessor and laser scatter sensing technologies for reliable, stable measurements with a response time of ≤ 10 seconds. Its streamlined enclosure allows for flexible installation and maintenance-free operation in typical indoor air quality applications. PM10 Air Quality Transmitter: AVC-510 Series AECL Explore now
AVC-310 and AVC-311 Series are advanced CO2 sensors utilizing non-dispersive infrared (NDIR) technology for accurate and stable CO2 measurements. The AVC-311 also includes temperature and humidity sensing capabilities, enhancing overall air quality monitoring. Both models support analog outputs, RS485 Modbus RTU interfaces, and SPDT dry contact outputs, making them suitable for applications in HVAC and BMS systems. CO2, Temperature and Humidity Transmitter : AVC-310 & AVC 311 Series AECL Explore now
The AVC-010 Oxygen Transmitter is designed to measure oxygen concentration to prevent critical decreases in O2 levels and to control the absence of oxygen in gas mixtures. It utilizes an advanced electrochemical oxygen sensing element to ensure stability and accuracy in measurement. Oxygen Transmitter: AVC-010 Series AECL Explore now
The Temperature and Humidity Transmitter is perfect for temperature and RH measurement in high humidity environment. Its special metal sintered sensing probe provides protection for the sensing elements and avoids the measurement outage which might happen in high humidity environment. Temperature Transmitter / Transmitter for Humidity or Dew Point: AHT-5 Series AECL Explore now
The AVC-910 TVOC Air Quality Transmitter is designed to measure total volatile organic compounds (TVOCs) ranging from 125 to 600ppb. It features a built-in MEMS metal oxide sensing element for excellent measurement performance and long-term stability. With RS485 signal output via Modbus RTU protocol, it easily integrates with BMS systems. TVOC Air Quality Transmitter: AVC-910 Series AECL Explore now
The Carbon Monoxide Transmitter uses an electrochemical sensing element to reliably monitor CO concentration in areas such as loading docks, underground parking, basements, garages, or boiler rooms. It offers switchable measurement ranges of 0 to 100ppm and 0 to 250ppm, with an optional high range of 30 to 1000ppm. Carbon Monoxide Transmitter: AVC-110 Series AECL Explore now
The Carbon Dioxide Transmitter is specially designed for measuring CO2 in high humidity environment. The featured metal sintered probe of the CO2 Transmitter with IP54 rating could protect the sensing electronics from the damage caused by moisture in the air to extend the life span of the sensing electronics. CO2 Transmitter for High Humidity: AVC-320 Series AECL Explore now Address: 729 Ba Thang Hai St., Dien Hong Ward, HCM City