Indoor Air Quality Transmitter: AVC-M Series AECL

The transmitter features industrial-standard RS485 Modbus RTU signal output for reliable integration into HVAC and BMS systems.

Application

  • Commercial building / office / meeting room.
  • Train Station.
  • Library.
  • Classroom.
  • Museum.
  • Food warehouse.
  • Parking lot.
  • Training center.
  • Train station.
  • Shopping Mall.
  • Indoor places where would be required to measure the illumination.
AVC-M_Catalog AVC-M_Manual +(84) 839 606 568

The AVC-M Indoor Air Quality Transmitter features high-quality sensors for measuring temperature, humidity, CO, CO2, PM2.5, PM10, TVOC, HCHO, oxygen, and NH3. With an RS485 Modbus RTU signal output, it is ideal for HVAC and BMS systems, offering a compact design for flexible integration. Recommended installation height is 1 to 2 meters above floor level.

Detail Up to top

Specification

ParametersTemperature, Humidity, CO2, CO, HCHO, TVOC, PM2.5, PM10, O2, O3, NH3, H2S, NO2, CL2
Signal outputRS485 or RS485 / LoRa (Peer to Peer) switchable, LoRa frequency band: 862 ~ 932 MHz(1)
Warm-up time15 minutes
Operating environment-10 ~ 50℃ (14~122℉) / 0 ~ 95%RH, non-condensing
Storage temperature -10 ~ 50℃ (14~122℉)
Power supplyDC 12 ~ 36V, AC 24V (50/60Hz)
Power consumption RS485: 3W (Max.); LoRa / RS485: 4.5W (Max.)
CertificationsCE, FCC
IP ratingIP30 (No protection from liquids)
Case materialFireproof ABS
Weight125g
 
Temperature MeasurementHumidity Measurement
Sensing element CMOS sensing elementCMOS sensing element
Measurement range-10.00 ~ 50.00℃ (14~122℉)0 ~ 99.99%RH
Accuracy± 0.3℃ (typical)± 3%RH (typical)
Resolution 0.01℃0.01%RH
Repeatability± 0.1℃± 0.1%RH
Response time 5 ~ 30 sec. (τ63%, 25℃)< 8 sec. (τ63%, 25℃)
Long-term drift< 0.04℃ / year< 0.5%RH / year
CO MeasurementHCHO Measurement
Measurement principleElectro-chemicalElectro-chemical
Measurement range0 ~ 100 ppm0 ~ 3.00 ppm
Accuracy (at 25℃)± 5%± 5%
Resolution 1 ppm0.01 ppm
RepeatabilityReading ± 2%< ± 0.05 ppm
Response time τ90≦30 secτ90 < 120 sec. (HCHO: 1 ppm)
DriftZero: < ± 5 ppm; Span: ≦5% reading / yearZero: < 0.05 ppm; Span: < 20% reading / year
CO2 MeasurementVOC Measurement
Measurement principleNDIR with automatic calibrationCMOS sensing element
Measurement range0 ~ 9999 ppm0 ~ 500 VOC Index points 0 ~ 500 ppb
Accuracy0 ~ 2000 ppm (± 30 ppm ± 3% of reading), 2001~9999 ppm (± 70 ppm ± 3% of reading)< ± 15 VOC Index points; < ± 20 ppb
Resolution 1ppm1 VOC Index points; 1 ppb
Repeatability± 20 ppm+ (± reading *1%)< ± 5 VOC Index points; < ± 15 ppb
Response time 2 minutes by 90%< 10 sec. (τ63%)
MaintenanceMaintenance-free for normal indoor applications
PM2.5 MeasurementPM10 Measurement
Measurement principleLaser distributingLaser distributing
Measurement range0 ~ 600 μg/m30 ~ 600 μg/m3
Accuracy0 ~ 100 μg/m3 (± 10 μg/m3), 100 ~ 600 μg/m3 (± 10%)0 ~ 100 μg/m3 (± 10 μg/m3), 100 ~ 600 μg/m3 (± 10%)
Resolution 1 μg/m31 μg/m3
Response time≦10 sec.≦10 sec.
MaintenanceMaintenance-free for normal indoor applicationsMaintenance-free for normal indoor applications
O2 MeasurementNH3 Measurement
Measurement principleElectro-chemicalElectro-chemical
Measurement range0 ~ 30%0 ~ 50.0 ppm
AccuracyFull scale ± 5%± 5%
Resolution 0.01%0.1 ppm
RepeatabilityReading ± 5%± 10%
Response time τ90≦15 sec.τ90≦90 sec.
Drift<2% / monthZero: < ± 10 ppm / year; Span: < 2% reading / month
CL2 MeasurementH2S Measurement
Measurement principle Electro-chemicalElectro-chemical
Measurement range0 ~ 5.00 ppm0 ~ 50.0 ppm
Accuracy± 5% for 0 ~ 5.00ppm± 5% for 0 ~ 50.0ppm
Resolution 0.01 ppm0.1 ppm
RepeatabilityReading ± 2%Reading ± 2%
Response time τ90≦30 secτ90≦60 sec
Drift≦2% / monthZero: < ± 0.1 ppm / year; Span: < 10% reading / year
O3 MeasurementNO2 Measurement
Measurement principleElectro-chemicalElectro-chemical
Measurement range0 ~ 5.00 ppm0 ~ 5.00 ppm
Accuracy± 5% for 0 ~ 5.00ppm± 5% for 0 ~ 5.00ppm
Resolution 0.01 ppm0.1 ppm
RepeatabilityReading ± 2%Reading ± 2%
Response time τ90≦30 secτ90≦30 sec
Drift≦10% / year≦10% / year
  Note:
  • In normal IAQ applications. Accuracy is defined after minimum 3 weeks of continuous operation with ABC. However, some industrial applications do require maintenance.
  • Note 2: Accuracy is specified at room temperature +25°C and at normal pressure 101.3 kPa. Specification is referenced to certified calibration mixtures. Uncertainty of calibration gas mixtures (±1% currently) is to be added to the specified accuracy for absolute measurements.
  • The frequency channels will be differed by country and this frequency can be configured accordingly from 862 to 932Hz.
  • It is recommended to perform calibration at least every 6 months. Meanwhile, for the device installed in the environment with extreme condition, quarterly calibration would be necessary. When sensor is aging (lifespan of sensor is usually 12 months), it might cause sensor drift.
  • VOC index points: The value 100 refers to the typical indoor gas composition over the past 24h. While values between 100 and 500 indicate a deterioration, values between 0 and 100 inform about improvement of the air quality.

Feature

  • Measurements: Temperature, Humidity, CO, CO2, PM2.5, PM10, TVOC, HCHO, Oxygen and NH3
  • Installation: Wall-mount
  • Protection: IP30
  • Optional bright LCD display.
  • CE & FCC Certifications.

Related products Up to top

HEADQUARTERS

Address: 729 Ba Thang Hai St., Dien Hong Ward, HCM City

Email: info@bkic.vn

Website: https://bkic.vn

HỒ CHÍ MINH OFFICE

Address: No. 4, Street 59, Binh Trung Ward, Ho Chi Minh

Email: info@bkic.vn

Website: https://bkic.vn

HÀ NỘI OFFICE

Address: No. 35, Lane 45, Tran Thai Tong Street, Cau Giay Ward, Ha Noi

Email: info@bkic.vn

Website: https://bkic.vn

Our clients