Carbon dioxide/volatile organic compound transmitters: Series CDTV DWYER

Simultaneously Outputs Both CO2 / VOC

Application

  • HVAC applications in hospitals, schools, and commercial buildings
  • Demand control ventilation
  • Odor control
  • Waiting rooms or other spaces that may be occupied 24 hours a day
CDTV.i AQ_CDTV_N AQ_CDTV_D (+84) 903 999 357

Carbon Dioxide/Volatile Organic Compound Transmitters, range: CO2: 0 to 2000 or 0 to 5000 ppm (depending on model); VOC: 0 to 2000 ppm CO2 equivalent, accuracy:CO2: ±40 ppm ±3% of reading.

Detail Up to top

Specification

Range:CO2: 0 to 2000 or 0 to 5000 ppm (depending on model); VOC: 0 to 2000 ppm CO2 equivalent.
Accuracy:CO2: ±40 ppm ±3% of reading.
Temperature Dependence:±8 ppm / °C at 1100 ppm.
Non-Linearity:CO2: 16 ppm.
Pressure Dependence:CO2: 0.13% of reading per mm of Hg.
Response Time:CO2: 2 minutes for 99% step change; VOC: 5 minutes.
Temperature Limits:32 to 122°F (0 to 50°C).
Duct Air Velocity Range:0-4000 FPM (20.32 m/s).
Power Requirements:16-35 VDC / 19-28 VAC.
Power Consumption:Average: 2 watts; Peak: 3.75 watts.
Sensor:CO2: Single-beam, dual-wavelength NDIR; VOC: MEMS metal oxide semiconductor.
Output:Current: 0-20 mA, 4-20 mA, 0-10 mA, or 2-10 mA (depending on selection jumper, max 500 Ω); Voltage: 0-10 VDC, 2-10 VDC, 0-5 VDC, or 1-5 VDC (depending on selection jumper, min 500 Ω); Relay: SPST NO 2A @ 30 VDC.
Weight:5.6 oz (158.8 g).
Enclosure Rating:Duct mount: NEMA 4X (IP66) for housing only; Wall mount: IP20.
Agency Approvals:CE.
Description: The Series CDTV Carbon Dioxide/Volatile Organic Compound (VOC) Transmitter reduces energy cost in buildings by lowering the amount of conditioned air based on the occupancy of the space. By sensing both CO2 and VOC, the transmitter can detect fumes that may need to be exhausted during lower occupancy periods.

Feature

  • Combination VOC and CO2 outputs reduce labor and material costs
  • Single beam dual wavelength NDIR CO2 sensor allows for use in spaces that may be occupied 24 hours a day
  • VOC output is correlated to be equivalent to CO2 measurements
  • Ventilate using ASHRAE’s occupancy-based VRP Algorithm
 

  Posted by Lam Thanh

Related products Up to top

HEADQUARTERS

Address: 729 Ba Thang Hai St., Dien Hong Ward, HCM City

Email: info@bkic.vn

Website: https://bkic.vn

HỒ CHÍ MINH OFFICE

Address: No. 4, Street 59, Binh Trung Ward, Ho Chi Minh

Phone: (+84) 903 999 357

Email: info@bkic.vn

Website: https://bkic.vn

HÀ NỘI OFFICE

Address: No. 35, Lane 45, Tran Thai Tong Street, Cau Giay Ward, Ha Noi

Phone: (+84) 915 141 176

Email: info@bkic.vn

Website: https://bkic.vn

Our clients