I/O Modules: MIX – IP Series – iSMA-Controlli

Equipped with Fast Ethernet ports and RS485 interface functioning as a Modbus TCP/IP to Modbus RTU/ASCII gateway, supporting seamless integration with other devices.

Application

  • Suitable for distributed control systems in building automation, HVAC, and data centers.
  • Used in projects requiring IP-based communication with building controllers.
  • Ideal for expanding system capacity through both new and existing BMS installations, enabling real-time data monitoring and control.
iSMA-B-MIX-IP_Datasheet_DBL681en_V1.0 iSMA-B-MIX18-IP_Installation_instruction_DIM407en_v4.4 iSMA-B-MIX38-IP_Installation_instruction_DIM409en_v4.5 +(84) 839 606 568

The MIX-IP series multiprotocol I/O modules extend the capabilities of controllers like MAC36NL, iSMA-B-J8, or AAC20 using IP connections and open communication protocols such as BACnet IP and Modbus TCP/IP. They provide the most commonly used types of I/Os in building automation, and support multiple modules via daisy chain connections.

Detail Up to top

Specification

Model:iSMA-B-MIX38iSMA-B-MIX18
Power Supply:DC: 24 V ± 20%, 7.4 W; AC: 24 V ± 20%, 11.1 VADC: 24 V ± 20%, 4.4 W; AC: 24 V ± 20%, 6.6 VA
Universal inputs:8x voltage, current and resistance measurement, dry contact5x voltage, current and resistance measurement, dry contact
Digital inputs:12x dry contact input, high-speed pulse counter up to 100 Hz5x dry contact input, high-speed pulse counter up to 100 Hz
Analog outputs:6x 0-10 V DC output, maximum load up to 20 mA per channel, 60 mA maximum total load for analog outputs4x 0-10 V DC output, maximum load up to 20 mA per channel, 60 mA maximum total load for analog outputs
Digital outputs:12x relay outputMaximum ratingsUL compliant ratings4x relay outputMaximum ratings UL compliant ratings
Resistive load max3 A @ 230 V AC 3 A @ 30 V DC3 A @ 24 V AC 3 A @ 30 V DCResistive load max3 A @ 230 V AC 3 A @ 30 V DC3 A @ 24 V AC 3 A @ 30 V DC
Inductive load max.75 VA @ 230 V AC 30 W @ 30 V DC8 VA @ 24 V AC 30 W @ 30 V DCInductive load max.75 VA @ 230 V AC 30 W @ 30 V DC8 VA @ 24 V AC 30 W @ 30 V DC
Interface:RS485 half-duplex, Modbus or BACnet, up to 128 devices on the bus, Ethernet, Modbus TCP/IP or BACnet IP
Address:Set by switch in the range from 0 to 99
Baudrate:Set by switch in the range from 4800 to 115200 bps
Ingress protection rating:IP40 - for indoor installation
Temperature:Operating: -10°C to +50°C (14°F to 122°F) Storage -40°C to +85°C (-40°F to +185°F)
Relative humidity:5 to 95% RH (without condensation)
Connectors:Separable, max 2.5 mm2 (18–12 AWG)
Dimensions:160x110x62 mm (6.30x4.33x2.44 in)88x110x62 mm (3.46x4.33x2.44 in)
Mounting:DIN rail mounting (DIN EN 50022 norm)
Housing material:Plastic, self-extinguishing PC/ABS

Feature

  • Mix of all I/O types
  • BACnet IP and Modbus TCP/IP protocols, selected with a DIP switch
  • Built-in Modbus TCP/IP to Modbus RTU/ASCII gateway
  • 2 Fast Ethernet ports with a built-in switch
  • Digital inputs work as fast counters up to 100 Hz
  • Universal inputs have 16-bit resolution, which increases the accuracy of measurement
  • Wide range of supported temperature sensors in Celsius and Fahrenheit degrees (NTC, PT1000, etc.)
  • Automatic detection of a signal type of universal inputs
  • Digital outputs 230 V AC max. 3 A allow for a direct control without additional relays
  • Analog outputs with max. 20 mA load per channel (60 mA maximum total load) allow for direct control of relays (12 V DC) or SSR with PWM support
  • LEDs indicate the status of inputs and outputs
  • Simple and fast addressing 0-99 using rotary switches
  • UL listed
  • BTL certified

HEADQUARTERS

Address: 729 Ba Thang Hai St., Dien Hong Ward, HCM City

Email: info@bkic.vn

Website: https://bkic.vn

HỒ CHÍ MINH OFFICE

Address: No. 4, Street 59, Binh Trung Ward, Ho Chi Minh

Email: info@bkic.vn

Website: https://bkic.vn

HÀ NỘI OFFICE

Address: No. 35, Lane 45, Tran Thai Tong Street, Cau Giay Ward, Ha Noi

Email: info@bkic.vn

Website: https://bkic.vn

Our clients