I/O Modules: MINI – RS Series – iSMA-Controlli

Supports Modbus RTU/ASCII and BACnet MS/TP protocols with built-in algorithms for lighting, cooling, and heating, enabling use as standalone controllers or as part of a larger BMS.

Application

  • Ideal for building automation, including lighting, cooling, and heating control.
  • Suitable for projects requiring manually operated switches and standalone control capabilities.
  • Used as extensions for controllers in both new and existing BMS installations, particularly for occupancy sensor applications.
iSMA-B-MINI-RS_Datasheet_DBL678en_V1.0 iSMA-B-8U_Installation_instruction_DIM422en_v3.3 iSMA-B-8I_Installation_instruction_DIM420en_v3.3 iSMA-B-4U4O-H_Installation_instruction_DIM418en_v3.3 iSMA-B-4TO-H_Installation_instruction_DIM414en_v3.3 iSMA-B-4O-H_Installation_instruction_DIM412en_v3.3 iSMA-B-4I4O-H_Installation_instruction_DIM410en_v3.3 iSMA-B-4U4A-H_Installation_instruction_DIM416en_v3.4 (+84) 903 999 357

The MINI-RS series multiprotocol I/O modules are compact remote I/O devices that extend building controllers with inputs and outputs over RS485 using open protocols such as BACnet MS/TP and Modbus RTU/ASCII. They are designed for easy integration with BMS, offering a cost-effective solution for building control systems.

Detail Up to top

Specification

Model: 4U-4A-H8U4U4O-H4I-4O-H8I4O-H4TO-H
Power supply:24 V AC/DC ± 20%
Universal inputs:Number of inputs:484............
Voltage input:Voltage measurement: 0-10 V DC Input impedance: 100 kΩ Measurement accuracy: ±0.1% Measurement resolution: 3 mV at 12-bit and 1 mV at 16-bit............
Current input:Current measurement: 0-20 mA Required external resistor: 200 Ω Measurement accuracy: ±1.1% Measurement resolution: 15 µA at 12-bit and 5 µA at 16-bit............
Digital input:Output current ~1 mAi............
Resistance input:Measurement of resistance: 0-1000 kΩ Measurement resolution for 20 kΩ load: 20 Ω at 12-bit and 1 Ω at 16-bit Measurement resolution for PT1000 and NI1000: 0.1 Ω at 16-bit Resistance measurement method: voltage divider............
Temperature input:Measurement with RTDS (Real Time Digital Simulator) attached Accuracy: ±0.1˚C The PT1000 and NI1000 sensors use 16-bit resolution............
Measurement resolution:12-bit (default), 16-bit............
Processing time:10 ms/channel at 12-bit 140 ms/channel at 16-bit............
Digital inputs:Number of inputs.........48......
Type:.........Dry contact or fast pulse counter......
Maximum input frequency:.........100 Hz saved in the EEPROM memory......
Analog outputs:Number of outputs4..................
Voltage range:0-10 V DC..................
Maximum load current:20 mA..................
Resolution:12-bit..................
Accuracy:±0.5%..................
Digital outputs:Number of outputs...............4...
Resistive load (AC1):......

UL compliant ratings: 3 A at 24 V AC 3 A at 30 V DC

Maximum ratings: 3 A at 230 V AC 3 A at 30 V DC

...

UL compliant ratings: 8 A at 230 V AC 8 A at 30 V DC

Maximum ratings: 8 A at 230 V AC 8 A at 30 V DC

...
Inductive load (AC3):......

UL compliant ratings: 8 VA at 24 V AC 30 W at 30 V DC

Maximum ratings: 75 VA at 230 V AC 30 W at 30 V DC

...

UL compliant ratings: 37 VA at 230 V AC 90 W at 30 V DC

Maximum ratings: 360 VA at 230 V AC 90 W at 30 V DC

...
Triac outputs:Number of outputs:..................4TO-H
Load:..................0.5 A at 20 V AC up to max. 250 V AC
Peak load per channel:..................1.5 A at 20 V AC up to max. 250 V AC (30 s)
Gate control:..................Zero crossing turn ON
Frequency range:..................47 to 63 Hz
Snubber:..................Snubberless triac
COM1:RS485 interface Half-duplex, Up to 128 devices
Communication protocolModbus RTU/ASCII, BACnet MS/TP
PortsScrew connector
Baud rate2400-115200
Address0-99 set by a rotary switch
USB1USB 2.0mini USB type B
Ingress protectionIP ratingIP 40 for indoor installation
TemperatureStorage-40°C to +85°C (-40°F to +185°F)
Operating-10°C to +50°C (14°F to 122°F)
HumidityRelative5 to 95% RH (without condensation)
Screw connectorsTypeRemovable screw terminals
Maximum cable size2.5 mm2 (18…12 AWG)
HousingMaterialSelf-extinguishing plastic (PC/ABS)
MountingDIN (DIN EN 50022 norm)
DimensionsWidth36.30 mm/1.43 in
Length114.40 mm/4.39 in
HeightWithout hand switch: 62.00 mm/2.44 in  || With hand switch: 68.70 mm/2.70 in

Feature

  • 7 different types of modules with RS485 communication
  • BACnet MS/TP, BACnet Slave, and Modbus RTU/ASCII protocols, selected with a DIP switch
  • Compact dimensions
  • Manual override switches*
  • Built-in HVAC and light applications**
  • All digital inputs work as fast counters up to 100 Hz
  • Universal inputs have 16-bit resolution, which increases the accuracy of measurement
  • Wide range of supported temperature sensors in Celsius and Fahrenheit degrees (NTC, PT1000, etc.)
  • Automatic detection of a signal type of universal inputs
  • Digital outputs 230 V AC max. 3 A or 8 A allow for direct control without additional relays
  • Triac outputs: 0.5 A at 24 V AC, 0.5 A at 230 V AC
  • Analog output with max. 20 mA load per channel allows for a direct control of relays (12 V DC) or SSR with PWM support
  • LEDs indicate the status of inputs and outputs
  • Simple and fast addressing from 0 to 99 using rotary switches
  • UL listed
  • BTL certified

HEADQUARTERS

Address: 729 Ba Thang Hai St., Dien Hong Ward, HCM City

Email: info@bkic.vn

Website: https://bkic.vn

HỒ CHÍ MINH OFFICE

Address: No. 4, Street 59, Binh Trung Ward, Ho Chi Minh

Phone: (+84) 903 999 357

Email: info@bkic.vn

Website: https://bkic.vn

HÀ NỘI OFFICE

Address: No. 35, Lane 45, Tran Thai Tong Street, Cau Giay Ward, Ha Noi

Phone: (+84) 915 141 176

Email: info@bkic.vn

Website: https://bkic.vn

Our clients