(+84) 903 999 357The SERIES RHP Temperature and Humidity Transmitter combine the voltage or current humidity transmitter output with a passive temperature thermistor or RTD output.
| Accuracy, Thermistor Temp Sensor: | ±0.2°C @ 25°C (±0.36°F @ 77°F). |
| Accuracy, RTD Temp Sensor: | DIN Class B; ±0.3°C @ 0°C (±0.54°F @ 32°F). |
| Accuracy, Solid State Band Gap: | ±0.9°F @ 77°F (±0.3°C @ 25°C). |
| Hysteresis: | ±1%. |
| Repeatability: | ±0.1% typical. |
| Temperature Limits: | -40 to 140°F (-40 to 60°C). |
| Storage Temperature: | -40 to 176°F (-40 to 80°C). |
| Compensated Temperature Range: | -4 to 140°F (-20 to 60°C). |
| 4 to 20 mA Loop Powered Models: | Power requirements: 10 to 35 VDC; Output signal: 4 to 20 mA. |
| 0-5/10 V Output Models: | Power requirements: 15 to 35 VDC or 15 to 29 VAC; Output signal: 0 to 10 V @ 5 mA max. |
| Solid State Band Gap Temp Sensor Output Ranges: | Switch selectable, -20 to 140°F (-28.9 to 60°C); 0 to 100°F (-17.8 to 37.8°C); 40 to 90°F (4.4 to 32.3°C); -4 to 140°F (-20 to 60°C). |
| Response Time: | 15 seconds. |
| Electrical Connections: | Removable screw terminal block. |
| Conduit Connection: | Duct Mount: 1/2" NPS; OSA: 1/2" (22.3 mm). |
| Drift: | <1% RH/year. |
| RH Sensor: | Capacitance polymer. |
| Temperature Sensor: | >Types 1, 2, 3: Solid state band gap; Curves A,B,C; Thermistor; Curves D,E; Platinum RTD DIN 385. (See R-T Lookup Table). |
| Enclosure: | Duct Mount: PBT; OSA: Polycarbonate. |
| Enclosure Rating: | NEMA 4X (IP66) for OSA mount only. |
| Display: | Duct Mount only, optional 2-line alpha numeric, 8 characters/line. |
| Display Resolution: | RH: 0.1%; 0.1°F (0.1°C). |
| Weight: | Duct Mount: .616 lb (.3 kg); OSA: 1 lb (.45 kg). |
| Agency Approvals: | CE. |
Posted by Tuan
THE SERIES GSTC Carbon Monoxide/Nitrogen Dioxide Gas Transmitter monitors the gas concentration in underground parking garages and loading docks. The carbon monoxide transmitter is used to measure the exhaust of gasoline engines, while the nitrogen dioxide transmitter is used for diesel engines. Carbon monoxide transmitters: Series GSTA & GSTC DWYER Explore now
The Series CMS300 Carbon Monoxide Transmitter and Switch provides a field selectable current or voltage output that is proportional to the carbon monoxide concentration in underground parking garages, vehicle maintenance facilities, or mechanical rooms. Carbon monoxide transmitter and switch: Series CMS300 DWYER Explore now Address: 729 Ba Thang Hai St., Dien Hong Ward, HCM City
Email: info@bkic.vn
Website: https://bkic.vn
Address: No. 4, Street 59, Binh Trung Ward, Ho Chi Minh
Phone: (+84) 903 999 357
Email: info@bkic.vn
Website: https://bkic.vn
Address: No. 35, Lane 45, Tran Thai Tong Street, Cau Giay Ward, Ha Noi
Phone: (+84) 915 141 176
Email: info@bkic.vn
Website: https://bkic.vn