(+84) 903 999 357THE SERIES GSTC Carbon Monoxide/Nitrogen Dioxide Gas Transmitter monitors the gas concentration in underground parking garages and loading docks. The carbon monoxide transmitter is used to measure the exhaust of gasoline engines, while the nitrogen dioxide transmitter is used for diesel engines.
| Sensor: | Field replaceable electrochemical, 4 years typical lifespan. |
| Range: | CO: 0 to 500 PPM, NO2: 10 PPM. |
| Output Drift: | <5% per year in air. |
| Coverage Area: | 5000 to 7500 sq ft typical. |
| Accuracy: | CO: 2% FS, NO2: 3% FS, at the time of calibration. |
| Resolution: | CO: 1 PPM; NO2: 0.1 PPM. |
| Temperature Limits: | -4 to 122°F (-20 to 50°C). |
| Storage Temperature: | For best sensor life, 32 to 68°F (0 to 20°C). |
| Humidity Limits: | 15 to 90% RH constant; 0 to 99% RH intermittent. |
| Response Time: | <45 s to 90% CO, <25 s to 90% NO2. |
| Span and Zero Adjustment: | Via pushbutton, using optional A-449 display. Zero only via BACnet or MODBUS® communication protocol. |
| Housing: | UV resistant glass filled polycarbonate. |
| Output Signals: | BACnet MS/TP, MODBUS® RTU, or MODBUS® ASCII (switch selectable) communication protocol. |
| Power Requirements: | 10 to 36 VDC or isolated 21.6 to 33 VAC. |
Posted by Tuan
The Series CMS300 Carbon Monoxide Transmitter and Switch provides a field selectable current or voltage output that is proportional to the carbon monoxide concentration in underground parking garages, vehicle maintenance facilities, or mechanical rooms. Carbon monoxide transmitter and switch: Series CMS300 DWYER Explore now Address: 729 Ba Thang Hai St., Dien Hong Ward, HCM City
Email: info@bkic.vn
Website: https://bkic.vn
Address: No. 4, Street 59, Binh Trung Ward, Ho Chi Minh
Phone: (+84) 903 999 357
Email: info@bkic.vn
Website: https://bkic.vn
Address: No. 35, Lane 45, Tran Thai Tong Street, Cau Giay Ward, Ha Noi
Phone: (+84) 915 141 176
Email: info@bkic.vn
Website: https://bkic.vn