The SERIES CDTA Communicating Carbon Dioxide Detector combines the function of three room sensors into a single, compact housing. Parameters include carbon dioxide, humidity, temperature, and temperature set point with override.
Sensor (CO2): | Single-beam, dual-wavelength NDIR; Humidity: Capacitive polymer; Temperature: 10KΩ thermistor. |
Range: | CO2: 0 to 2000 or 5000 PPM CO2 (depending on model); Humidity: 0 to 100% RH; Temperature: 32 to 122°F (0 to 50°C). |
Accuracy: | CO2: ±40 ppm ±3% of reading; RH: ±2% (10 to 90% RH); Temperature: ±1°C @ 25°C. |
Temperature Dependence (CO2): | ±8 ppm / °C at 1100 ppm. |
Non-Linearity (CO2): | 16 ppm. |
Pressure Dependence (CO2): | 0.13% of reading per mm of Hg. |
Response Time (CO2): | 2 minutes for 99% step change. |
Temperature Limits: | 32 to 122°F (0 to 50°C). |
Humidity Limits: | 10 to 95% RH (non-condensing). |
Power Requirements: | 10 to 42 VDC / 10 to 30 VAC. |
Power Consumption: | Average: 0.5 watts; Peak: 1.2 watts. |
Output: | 2-wire RS-485, Modbus® RTU or BACnet MS/TP communication protocol. |
Weight: | 5.6 oz (158.8 g). |
Agency Approvals: | BTL, CE. |
Posted by Tuan
Address: 729 Ba Thang Hai St., Dien Hong Ward, HCM City
Email: info@bkic.vn
Website: https://bkic.vn
Address: No. 4, Street 59, Binh Trung Ward, Ho Chi Minh
Phone: (+84) 903 999 357
Email: info@bkic.vn
Website: https://bkic.vn
Address: No. 35, Lane 45, Tran Thai Tong Street, Cau Giay Ward, Ha Noi
Phone: (+84) 915 141 176
Email: info@bkic.vn
Website: https://bkic.vn