The RT-3000-P is a photoelectric weather tight duct smoke
detector. The weathertight, NEMA 4X rated, corrosion
resistant enclosure, coupled with extended temperature
listings, allow installation in the widest possible range of
indoor/outdoor environments.
Model number: | RT-3000-P Photoelectric: 230VAC, 115VAC, 24VAC, 24VDC |
Smoke sensor model number: | 55000-335DCT |
Sampling tubes: | FAST Tube Sectional sampling tube, kit fits up to 90” duct width |
STN-1.0 Sampling tube for 6” to 12” duct width | |
STN-2.5 Sampling tube for 1’ to 3’ duct width | |
STN-5.0 Sampling tube for 3’ to 5’ duct width | |
Power requirements: Standby: | 230VAC 12mA |
115VAC 22mA | |
24VAC 55mA | |
24VDC 14mA | |
Power requirements: Alarm: | 230VAC 18mA |
115VAC 32mA | |
24VAC 190mA | |
24VDC 68mA | |
Relay contact rating: Alarm contacts: | Resistive load: 2 sets form “C” rated at 10 Amps @ 115VAC |
Resistive load: 1 set form “A” rated at 2 Amps | |
Relay contact rating: Trouble contacts: | Resistive load: 1 set form “C” rated at 10 Amps @ 115VAC |
Air velocity: | 100 to 4,000 ft./min. |
Ambient temperature: | RT-3000-P -4°F to 140°F (-20°C to 60°C) |
Humidity: | 10% to 93% RH (@32°C) Non-Condensing / Non-Freezing |
Wiring: | Solid or stranded: #14 to #24 AWG terminals |
Approvals: | UL & CUL Listed (UL268A, UROX, UROX7) File # S2829 CSFM Listed (3240-1004:105) |
Material: | Grey plastic backbox, white plastic cover (Makrolon 94V-0) |
Dimensions: | 13 ½" L x 5 ½" W x 2 ¼" H |
Max. net wt.: | 3 ½ lbs. |
Hardware: | 7" exhaust tube, FAST Tube sectional sampling tube starter, sampling tube end cap, mounting template, test magnet, and mounting hardware included |
Address: 729 Ba Thang Hai St., Dien Hong Ward, HCM City
Email: info@bkic.vn
Website: https://bkic.vn
Address: No. 4, Street 59, Binh Trung Ward, Ho Chi Minh
Phone: (+84) 903 999 357
Email: info@bkic.vn
Website: https://bkic.vn
Address: No. 35, Lane 45, Tran Thai Tong Street, Cau Giay Ward, Ha Noi
Phone: (+84) 915 141 176
Email: info@bkic.vn
Website: https://bkic.vn