Gages-digital: Series DPG-200 DWYER

3-in-1: Gage, Transmitter and Switch

Application

  • Level Control
  • Pump Control
  • Process Control
  • Compressor Control
DPG-200_DSGT_Catalog DPG-200_iom (+84) 903 999 357

Digital Pressure Gage, accuaracy ±0.25% FS, NEMA 4X (IP66), pressure range: 0 – 5000 psi

Detail Up to top

Specification

DIGITAL GAGE SPECIFICATIONS
Service:Liquids and non-combustible compatible gases.
Wetted Materials:316L SS.
Enclosure:Black polycarbonate front & back cover, anodized aluminum extruded enclosure with recessed grooves, polycarbonate overlay, Buna-N O-rings, 316L SS sensor construction.
Accuracy:0.25% FS ±1 least significant digit (includes linearity, hysteresis, repeatability).
Pressure Limit:2x pressure range for models ≤ 1000 psi; 5000 psi for 3000 psi range; 7500 psi for 5000 psi range.
Temperature Limits:32 to 158°F (0 to 70°C).
Process Connection:1/4˝ male NPT
Display:4 digit (.425˝ H x .234˝ W digits).
Size:3.00˝ OD x 1.90˝ deep (not including cables).
Weight:8.84 oz (275 g).
SWITCH SPECIFICATIONS
Switch Type:2 SPDT form C contacts.
Electrical Rating:0.5 A @ 125 VAC resistive, 1 A @ 24 VDC.
Relay Differential:1 least significant digit.
Electrical Connections:3 ft (.91 m) cable.
Mounting Orientation:Mount in any position.
Set Point Adjustment:Via menu.
TRANSMITTER SPECIFICATIONS
Temperature Limits:0 to 158°F (0 to 70°C).
Thermal Effect:Between 70 to 158°F = 0.016%/°F. Between 0 to 70°F = 0.026%/°F.
Power Requirements:12-24 VAC ±20% 50 to 400 Hz, 12-24 VDC ±20%. Output Signal: 4-20 mA.
Loop Resistance:600 Ω max
Power Consumption:0.8 W max.
Electrical Connections:3 ft (.91 m) cable.
Enclosure Rating:Designed to meet NEMA 4X (IP66).
Description: The Series DPG-200 Digital Pressure Gage has a precise ±0.25% full scale accuracy. The 4 digit digital display will reduce the potential for errors in readings by eliminating parallax error commonly produced with analog gages. The DPG-200 is packaged in a durable extruded aluminum case designed to meet NEMA 4X (IP66). The unit is powered by 12-24 VDC/VAC and contains two alarm set points along with a 4-20 mA process output. A four-button keypad allows easy access to features. These features include backlight, peak and valley, auto zero and conversion of the pressure units.
Posted by Lam Thanh

Related products Up to top

HEADQUARTERS

Address: 729 Ba Thang Hai St., Dien Hong Ward, HCM City

Email: info@bkic.vn

Website: https://bkic.vn

HỒ CHÍ MINH OFFICE

Address: No. 4, Street 59, Binh Trung Ward, Ho Chi Minh

Phone: (+84) 903 999 357

Email: info@bkic.vn

Website: https://bkic.vn

HÀ NỘI OFFICE

Address: No. 35, Lane 45, Tran Thai Tong Street, Cau Giay Ward, Ha Noi

Phone: (+84) 915 141 176

Email: info@bkic.vn

Website: https://bkic.vn

Our clients